| HS Code | 385675 |
| Product Name | Dow ENDURANCE XLPE HFDB-4201 EC |
| Manufacturer | Dow |
| Material Type | Tree-Retardant Crosslinked Polyethylene (TR-XLPE) |
| Application | Medium Voltage Power Cable Insulation |
| Color | Natural |
| Form | Pellets |
| Density | 0.92 g/cm³ |
| Melt Index | 2.0 g/10 min |
| Dielectric Constant | 2.3 at 50 Hz |
| Dissipation Factor | 0.0005 at 50 Hz |
| Volume Resistivity | 1e16 ohm·cm |
| Dielectric Strength | 30 kV/mm |
| Tensile Strength | 15 MPa |
| Elongation At Break | 400% |
| Maximum Continuous Operating Temperature | 90°C |
| Crosslinking Method | Peroxide Cured |
| Water Tree Resistance | Yes |
| Halogen Free | Yes |
As an accredited Dow ENDURANCE XLPE HFDB-4201 EC factory, we enforce strict quality protocols—every batch undergoes rigorous testing to ensure consistent efficacy and safety standards.
| Packing | Dow ENDURANCE XLPE HFDB-4201 EC is supplied in 25 kg moisture-resistant bags, palletized for industrial handling and storage. |
| Container Loading (20′ FCL) | Dow ENDURANCE XLPE HFDB-4201 EC is palletized and loaded in a 20′ FCL container, protected from moisture and secured for stable transport. |
| Shipping | Dow ENDURANCE XLPE HFDB-4201 EC ships as a non-hazardous, non-regulated plastic compound in pellet form. No UN number, hazard class, or packing group applies. Keep packages closed and dry, protect from excessive heat, moisture, and contamination, and handle per the SDS. |
| Storage | Store Dow ENDURANCE XLPE HFDB-4201 EC in a cool, dry, well-ventilated area away from direct sunlight, heat, ignition sources, and moisture. Keep containers tightly closed and labeled, prevent contamination, protect from physical damage, and avoid prolonged storage above recommended temperatures. Follow the manufacturer’s SDS and local regulations; use first-in, first-out inventory. |
| Shelf Life | Shelf life: 24 months from manufacture when stored unopened in original packaging, dry conditions, and protected from direct sunlight. |
Across utility underground distribution cable lines producing 8.7/15 kV three-core or single-core designs, HFDB-4201 EC is extruded as the middle layer of a triple-layer co-extrusion structure in which semiconductive conductor shield, peroxide-curable XLPE insulation, and extruded semiconductive insulation shield are applied in one pass over compacted copper or aluminium conductors. The insulation melt is maintained in the range 115 °C to 125 °C at the extruder head, with screw-tip thermocouples held below 130 °C to prevent premature decomposition of the peroxide curing system. A nominal insulation thickness of 4.5 mm applies to 8.7/15 kV designs specified under IEC 60502-2; equivalent 15 kV class products specified for North American utilities use 4.45 mm at 100% insulation level under ICEA S-94-649. The compound is dosed gravimetrically as a ready-to-crosslink pellet blend, without letdown dilution or additional peroxide masterbatch, because the peroxide and antioxidant package is pre-dispersed during pellet manufacturing; post-blending with reground XLPE above 10 wt% is not recommended unless hot-set and tensile properties are re-qualified. Cure takes place in a dry-cure tube under nitrogen pressure, with line speed set to achieve cure state equivalent to hot-set elongation below 175% and permanent set below 15% when tested at 200 °C and 0.2 MPa in accordance with IEC 60811-507. The finished cable is supplied for direct burial, duct installation, or cable tray use in utility distribution loops, pad-mounted transformer feeds, and main-tie feeder circuits. Routine electrical tests include partial discharge below 10 pC at 1.73 U0, bending tests, load cycling, and impulse voltage at 95 kV for 15 kV 100% insulation level under IEC 60502-2 and AEIC CS8.
| Rated voltage U0/U | Nominal insulation thickness | Reference standard |
|---|---|---|
| 3.6/6 kV | 2.5 mm | IEC 60502-2 |
| 6/10 kV | 3.4 mm | IEC 60502-2 |
| 8.7/15 kV | 4.5 mm | IEC 60502-2 |
| 12/20 kV | 5.5 mm | IEC 60502-2 |
| 18/30 kV | 8.0 mm | IEC 60502-2 |
Wet-electrical aging in 18/30 kV sub-transmission insulation is governed by water-tree initiation at microvoids, contamination sites, and incidental protrusions from semiconductive shield interfaces. HFDB-4201 EC is selected on the basis of long-term wet-electrical performance rather than short-term dielectric strength alone; the compound contains a pre-dispersed tree-retardant system, and quantitative additive ratios are proprietary, so cable producers verify dispersion indirectly through melt contamination scanning and microvoid content audits instead of gravimetric batch records. A nominal insulation wall of 8.0 mm is applied under IEC 60502-2; this thicker wall increases residence time in the dry-cure tube, requiring nitrogen pressure and temperature profiling that removes peroxide decomposition byproducts such as acetophenone and methane while avoiding void formation at the conductor screen interface. Wet-electrical acceptance is commonly derived from utility specifications modeled on AEIC CS8 and ANSI/ICEA S-94-649-2013, with samples subjected to long-term immersion or water-filled conductor cycling before AC withstand and impulse testing. The terminal product is used in primary substation interconnections, distributed generation tie feeders, and 18/30 kV sub-transmission links where partially wet buried conditions are expected. Processing boundaries include storage below 50 °C, avoidance of surface moisture condensation above 60% RH, and prohibition of amine-containing color masterbatches because these can interfere with the peroxide cure and increase scorch tendency.
Melt homogeneity is controlled by a single-flight barrier screw with L/D between 24:1 and 30:1, a compression ratio near 3.0:1, and a mixing section that distributes peroxide decomposition products without excessive shear heating. Screen pack configurations typically range from 20 to 100 mesh depending on back-pressure target and melt filtration requirements; high back-pressure settings above 40 MPa are avoided because frictional heat can push melt temperature toward the scorch threshold. Barrel temperatures are profiled from 110 °C at the feed throat to 125 °C at the first metering zone, with head and die temperatures held no higher than 130 °C; residence time is kept below 10 min in the hot zones. Pellets do not require drying when warehouse relative humidity remains below 60%; if surface moisture is observed, hot-air drying at 60 °C for 2 h to 4 h is sufficient to remove condensation without reducing additive activity. The primary process failure is scorch, which appears as hard gel particles or rough insulation surface, and is managed by screw-speed reductions rather than barrel-temperature reductions below 105 °C, because low melt temperature compromises interfacial fusion with semiconductive shields. Terminal products processed under these constraints include 6/10 kV, 8.7/15 kV, and 12/20 kV distribution cables for continuous conductor operation at 90 °C, overload operation at 130 °C, and short-circuit operation at 250 °C.
On industrial motor feeder cable production lines serving refinery, chemical plant, and mining loads, HFDB-4201 EC is processed after a semiconductive conductor shield extrusion station for 5 kV class shielded constructions. The insulation wall thickness is set at 2.29 mm for 100% insulation level and 2.92 mm for 133% insulation level under ANSI/ICEA S-94-649-2013, with conductor sizes selected according to IEC 60228 or ASTM B3 for stranded copper. The cable is type-tested under UL 1072 or utility equivalent medium-voltage cable standards, including insulation resistance, conductor resistance, hot set, and high-potential AC withstand as specified by the applicable user standard. Unlike distribution cables, motor feeder constructions are frequently installed in continuous cable tray runs where repeated motor starts and harmonic loads raise conductor temperature; the insulation must therefore retain wet-set resistance and thermal-mechanical integrity during load cycling. The terminal product is a flexible industrial feeder cable that connects switchgear to large motors, variable-frequency drives, and process equipment, with bending radii and pulling tensions governed by installation specifications rather than material cure state. Process boundaries for this application include the same scorch-prevention limit of 130 °C melt temperature and avoidance of regrind addition above 10 wt% unless full type-test re-qualification is performed.
Renewable collector circuits using 12/20 kV three-core cables impose stricter dimensional control because the insulation layer is thicker than in 8.7/15 kV distribution products, at 5.5 mm under IEC 60502-2, and the cable must withstand frequent thermal cycling from intermittent wind or solar generation. The same compound is fed to the middle-layer extruder, but die sizing and haul-off speed are adjusted to maintain the specified insulation thickness at line speeds that preserve cure state. No additional UV stabilizer is added to the insulation compound because the XLPE layer is not exposed to sunlight in service; an outer polyethylene or PVC jacket is applied separately for direct burial or exposed tray installation. Compliance documentation for renewable collector cable includes IEC 60502-2 and, in China, GB/T 12706.2, with residual production tests for partial discharge and induced voltage after cable assembly. The terminal product is installed between turbine transformers or PV inverter stations and the collector substation, where cable lengths of 500 m to 1,500 m are common and conductor cross-sections typically range from 50 mm² to 630 mm². Processing boundaries include ambient humidity below 60% RH to avoid surface moisture on pellets and prohibition of post-extrusion moisture immersion before the insulation has cooled below 70 °C.
Before a 12/20 kV transformer-secondary cable enters routine production, type testing follows the IEC 60502-2 sequence: conductor and insulation dimensional checks, partial discharge at 1.73 U0 with background noise below 10 pC, bending, load cycling, impulse at 125 kV peak for 12/20 kV, and final AC withstand. HFDB-4201 EC must demonstrate stable hot-set values across the full reel length; samples are taken at inner, middle, and outer layers of the reel because cure variability along the cable length is a known failure mode on continuous vulcanization lines. The insulation is not formulated for direct contact with transformer oil, and cable terminations in oil-filled equipment require sealed barrier components or dry-type bushings to prevent oil absorption and swelling of the XLPE surface. Terminal product is a short, high-current transformer-secondary cable connecting the secondary terminals of pad-mounted or substation transformers to low-voltage or medium-voltage switchgear; conductor sizes are selected to match the transformer rating, and the cable is subjected to short-circuit current tests at the transformer’s rated duration of 1 s to 3 s with conductor temperature not exceeding 250 °C.
| Property | Test method | Typical acceptance |
|---|---|---|
| Hot set elongation | IEC 60811-507 | ≤ 175% elongation, ≤ 15% permanent set |
| Tensile strength before aging | IEC 60811-501 | ≥ 12.5 MPa |
| Elongation at break before aging | IEC 60811-501 | ≥ 200% |
| Volume resistivity at 20 °C | IEC 62631-3-1 | ≥ 1014 Ω·m |
| Partial discharge at 1.73 U0 | IEC 60885 | ≤ 10 pC |
Competitive Dow ENDURANCE XLPE HFDB-4201 EC prices that fit your budget—flexible terms and customized quotes for every order.
For samples, pricing, or more information, please contact us at +8618005193850 or mail to sales8@sinochem-nanjing.com.
We will respond to you as soon as possible.
Tel: +8618005193850
Email: sales8@sinochem-nanjing.com
Flexible payment, competitive price, premium service - Inquire now!