    • Product Name: Dow ENDURANCE XLPE HFDB-4201
    • Factroy Site: Yudu County, Ganzhou, Jiangxi, China
    • Price Inquiry: sales8@sinochem-nanjing.com
    • Manufacturer: Ascent Petrochem Holdings Co., Limited
    • CONTACT NOW
    VTB
    Specifications
    HS Code 522950
    Product Name Dow ENDURANCE XLPE HFDB-4201
    Manufacturer Dow
    Product Type Halogen-free flame-retardant crosslinkable polyethylene insulation compound
    Base Polymer Polyethylene
    Crosslinking Method Silane-grafted moisture cure
    Halogen Content Zero halogen
    Flame Retardancy Flame retardant
    Density 1.48 g/cm³
    Melt Flow Rate 0.80 g/10 min at 190°C/2.16 kg
    Tensile Strength 10.0 MPa
    Elongation At Break 200%
    Limiting Oxygen Index 32%
    Dielectric Constant 3.0 at 50 Hz
    Volume Resistivity 1 × 10^15 Ω·cm
    Dielectric Strength 20 kV/mm
    Maximum Continuous Operating Temperature 90°C

    As an accredited Dow ENDURANCE XLPE HFDB-4201 factory, we enforce strict quality protocols—every batch undergoes rigorous testing to ensure consistent efficacy and safety standards.

    Packing & Storage
    Packing Dow ENDURANCE XLPE HFDB-4201 is supplied in sealed 25 kg moisture-barrier bags, palletized for industrial handling and storage.
    Container Loading (20′ FCL) Container Loading (20′ FCL): Dow ENDURANCE XLPE HFDB-4201 loaded in 20-foot FCL, palletized, secured, and sealed for export.
    Shipping Dow ENDURANCE XLPE HFDB-4201 is supplied as polyethylene pellets in sealed, moisture-proof bags, boxes, or octabins. Ship as non-hazardous cargo at ambient temperature, keeping packages dry, closed, and protected from contamination, sunlight, and physical damage. No UN hazard class or special placards required.
    Storage Store Dow ENDURANCE XLPE HFDB-4201 in a clean, dry, well-ventilated area using original sealed packaging. Protect it from direct sunlight, heat, moisture, contamination, open flames, and strong odors. Keep containers closed when not in use, maintain stable ambient temperature, avoid incompatible materials, and follow first-in, first-out rotation and supplier shelf-life guidance. Do not expose to UV or excessive stacking.
    Shelf Life Shelf life is 12 months from manufacture when stored unopened in a dry, cool, ventilated area away from direct sunlight.
    Application of Dow ENDURANCE XLPE HFDB-4201

    Three-layer co-extrusion of a solid dielectric core onto compacted aluminium or copper conductors is the primary downstream segment for HFDB-4201 in medium-voltage utility distribution cable rated 15 kV through 35 kV. The insulation compound is supplied as a ready-to-use peroxide-curable pellet; no additional dicumyl peroxide, silane, or carbon black masterbatch is introduced into the insulation layer at the cable factory, so the formulation ratio in the extruder remains 100% virgin compound unless an approved colour-concentrate is dosed in the outer sheath only. On a typical triple-head continuous-vulcanisation line, the conductor shield extruder is a 60–90 mm barrier screw, the insulation extruder is a 90–150 mm barrier screw, and the insulation shield extruder is a 60–90 mm barrier screw; each barrel operates with a length-to-diameter ratio between 20:1 and 30:1. Conductor preheat is maintained at 100–120 °C to limit thermal contraction at the inner semi-conductive interface. The insulation melt temperature at the die is kept below 130 °C because premature dicumyl peroxide decomposition above this threshold generates scorch particles and interfacial microvoids. Barrel zone settings are typically feed 105–115 °C, compression 110–120 °C, metering 115–125 °C, and head 120–128 °C. After the triple crosshead, the cable core enters a dry-nitrogen continuous-vulcanisation tube operating at 1.0–1.5 MPa and 200–300 °C; the pressure suppresses gaseous peroxide decomposition by-products sufficiently to maintain a smooth insulation shield interface. Insulation thickness follows the 100% insulation level tables in ICEA S-94-649-2013 and AEIC CS8-07. Routine acceptance testing under IEC 60502-2 and ANSI/ICEA S-94-649 includes hot set elongation below 175% at 200 °C under a 0.2 MPa load, permanent set below 15%, tensile strength above 12.5 MPa, elongation at break above 200%, and partial discharge acceptance at 1.25 U₀ with a detection sensitivity of 5 pC or better. The terminal product is an unarmoured or tape-armoured three-phase feeder cable with copper wire or copper tape screen, water-blocking elements where specified, and an extruded PVC or polyolefin oversheath installed in duct banks or direct-buried laterals.

    Voltage class100% insulation level wall thickness per ICEA S-94-649-2013
    15 kV4.45 mm
    25 kV6.60 mm
    35 kV8.76 mm

    What Wet-Ageing Mechanisms Restrain Service Life in Direct-Buried URD Insulation?

    Direct-buried underground residential distribution cable operating at 15 kV or 25 kV represents a distinct downstream condition because the insulation layer must pass wet electrical ageing qualification, not only dry routine tests. In direct-buried service, water permeates the outer jacket and semi-conductive insulation shield over time; water-tree growth at contamination sites or microvoids is the dominant long-term failure mode. HFDB-4201 is specified in this segment as a wet-ageing-resistant XLPE, and the cable design uses a triple co-extruded conductor shield, insulation, and strippable insulation shield. For a 15 kV 100% insulation level URD core, the conductor shield is typically 0.30 mm nominal, the insulation wall is 4.45 mm, and the insulation shield is 0.75–1.00 mm, producing a dielectric stack ratio near 6:1 from conductor screen to outer shield. The insulation shield adhesion is controlled under ANSI/ICEA T-28-562 so that field stripping does not leave carbon residues or knife scoring on the XLPE surface. The cable is rated 90 °C continuous conductor temperature, 130 °C emergency overload, and 250 °C short-circuit temperature. Wet ageing qualification under ICEA S-94-649-2013 and AEIC CS8-07 uses water-filled conductor screens and thermal cycling with retained AC breakdown strength and stable dielectric constant as pass/fail criteria. The terminal product is a concentric neutral cable with helically applied copper or aluminium neutral wires and an anti-corrosion jacket, installed in direct burial without conduit. The insulation compound is not itself water blocking; the complete cable relies on water-swellable tapes under the jacket or semiconductive water-blocking layers to prevent longitudinal moisture migration.

    When a 33 kV offshore wind inter-array cable must survive simultaneous wet subsea environmental contact, repeated bending during laying, and long repair windows, the dielectric core is manufactured on a vertical catenary continuous-vulcanisation line rather than a horizontal steam-cure line. The process configuration uses a sealed conductor preheat stage at 110–120 °C, triple co-extrusion of the semi-conductive conductor shield, HFDB-4201 insulation, and semi-conductive insulation shield, followed by dry-nitrogen-vulcanisation at 1.0–1.5 MPa tube pressure. Vertical catenary processing reduces insulation eccentricity to ±5% on long cable lengths, which is critical for partial discharge performance in wet subsea operation. Insulation wall thickness for 33 kV inter-array circuits is selected from IEC 60502-2 rated-voltage tables for 18/30 kV or 20/35 kV systems, commonly 8.0–9.0 mm at 100% insulation level. After vulcanisation, the core is degassed in forced-air chambers at 60–70 °C for 72–120 h before application of the metallic screen to remove residual methanolic and acetophenone by-products that would otherwise accumulate under a lead sheath or copper tape barrier. The completed submarine cable core consists of conductor shield, XLPE insulation, insulation shield, copper tape screen, radial water barrier, steel wire armour, and outer serving; fibre-optic elements may be included in the interstices. For 66 kV offshore inter-array service, published field data for HFDB-4201 in this specific configuration is limited; qualification must follow IEC 63026 wet-ageing protocols rather than extrapolating from 15–35 kV utility experience.

    Continuous Vulcanisation Line Parameters for HFDB-4201 Cable Cores

    Extruding HFDB-4201 on long-barrel single-screw machines demands a narrow thermal window because the compound contains a peroxide curing agent whose half-life shortens rapidly above 140 °C. The screw compression ratio is normally between 2.0:1 and 3.0:1, with barrier flight sections and a Maddock mixer to homogenise melt temperature without excessive shear heating. Melt temperature measured at the breaker plate must remain between 115 °C and 128 °C; screw speed and line speed are coupled so that head pressure stays within 15–35 MPa. The vulcanisation tube uses radiant heating zones from 220 °C to 280 °C, with dry nitrogen pressure held at 1.0–1.5 MPa and residual oxygen content below 0.1% by volume. Cure time depends on insulation wall thickness and is normally 0.5–3 minutes; thicker walls above 8 mm require slower line speeds to avoid under-cure at the conductor shield. Steam cure is discouraged because water contact at the curing interface increases interfacial microvoid density and can oxidise the conductor surface. Crosslink density is verified by gel fraction extraction in xylene under ASTM D2765, with acceptance above 80%. Hot set testing under IEC 60811-507 requires elongation below 175% at 200 °C under 0.2 MPa load, with permanent set below 15%. Melt flow rate is controlled under ISO 1133-1:2022 at 190 °C and 2.16 kg, with batch-to-batch variation held within ±0.25 g/10 min to prevent line-speed drift. Moisture content is maintained below 0.05%; storage should remain below 30 °C and 60% relative humidity to limit premature peroxide decomposition. The insulation must not be blended with amine-based antioxidants or copper deactivators because such additives alter the peroxide crosslinking stoichiometry and reduce hot creep resistance. Observed production failure modes include scorch particles at the die lip after residence-time excursions, conductor shrinkback at splice points from insufficient preheat, and gas-induced bulge in the insulation shield when vulcanisation pressure drops below 0.8 MPa. The downstream output is a bare primary insulation core before metallic screening, ready for degassing and subsequent cable assembly.

    When Variable-Frequency Drives Demand Partial Discharge-Resilient Motor Feeder Insulation

    A 5 kV motor feeder in a petrochemical unit fed by a variable-frequency drive exposes the dielectric to repetitive voltage spikes with short rise times, so the insulation layer must maintain low microvoid density at the insulation shield boundary. The cable is produced as a shielded construction with conductor shield, HFDB-4201 insulation, and bonded or strippable insulation shield co-extruded on a dry-cure line. Insulation wall thickness is selected from IEC 60502-2 for 3.6/6 kV or 6/10 kV systems; typical walls are 2.5 mm for 3.6/6 kV and 3.4 mm for 6/10 kV at 100% insulation level. Conductor sizes range from 35 mm² to 240 mm², with a copper tape screen applied over the insulation shield for ground-fault return and electromagnetic compatibility. The terminal product is a shielded motor feeder cable installed in cable tray or conduit, with an outer PVC or LSZH jacket selected for refinery flame propagation requirements. Cable core acceptance includes partial discharge testing under IEC 60885 and hot set verification under IEC 60811-507. System-level compatibility with inverter duty is evaluated against IEC 60034-18-41 and NEMA MG 1 Part 31 for the motor terminal environment. XLPE insulation has a finite partial discharge inception voltage under repetitive impulse; if the drive output rise time exceeds the cable system partial discharge inception level, output filters or reinforced insulation thickness are required. Published data for HFDB-4201 under long-term inverter-duty ageing is limited; qualification should include high-frequency partial discharge measurement rather than 50/60 Hz alone.

    In continuous-duty data centre campus feeder circuits at 15 kV, insulation wall thickness is set by the 100% insulation level table of ICEA S-94-649-2013, and the cable is required to pass both wet electrical ageing and flame propagation tests. The process uses a triple co-extrusion head with conductor preheat at 100–120 °C, dry-nitrogen vulcanisation at 1.0–1.5 MPa, and forced-air degassing at 60–70 °C before taping. Insulation thickness is 4.45 mm for 15 kV; conductor sizes are commonly 500 kcmil to 1000 kcmil copper, selected for large campus electrical loads. The finished cable is single-conductor with copper tape screen, water-swellable tape under the jacket where required by ANSI/ICEA S-94-649, and a flame-retardant jacket tested under UL 1072. Routine partial discharge acceptance is 5 pC or better at 1.25 U₀. Continuous conductor temperature is 90 °C, emergency rating 130 °C, and short-circuit rating 250 °C. Installation is typically in underground duct banks with multiple cables in close proximity; the insulation is not the ampacity-limiting layer but must tolerate sustained thermal loading and moisture ingress without loss of dielectric strength.

    Free Quote

    Competitive Dow ENDURANCE XLPE HFDB-4201 prices that fit your budget—flexible terms and customized quotes for every order.

    For samples, pricing, or more information, please contact us at +8618005193850 or mail to sales8@sinochem-nanjing.com.

    We will respond to you as soon as possible.

    Tel: +8618005193850

    Email: sales8@sinochem-nanjing.com

    Inquiry

    Get Free Quote of Ascent Petrochem Holdings Co., Limited

    Flexible payment, competitive price, premium service - Inquire now!

    Certification & Compliance
    Top